6-82
Function code name
No.
Name Keypad
display
Setting
range
Description
When U-Ai1 is selected:
Universal Ai1(±16384/±10V) can be monitored.
U61
U-Ai1/
Pulse train position
command
monitor
USER P61
-32768 to
32767
When pulse data is selected:
Pulse train position command (PG(PR) input) data can be
monitored.
When U-Ai2 is selected:
Universal Ai2(±16384/±10V) can be monitored.
U62
U-Ai2/
Position detection
monitor
USER P62
-32768 to
32767
When pulse data is selected:
Position detection (internal or PG(PD) input) data can be
monitored.
When U-Ai3 is selected:
Universal Ai3(±16384/±10V) can be monitored.
U63
U-Ai3/
Position detection
(Z-phase input)
monitor
USER P63
-32768 to
32767
When pulse data is selected:
Position detection (PG(PD) Z-phase input) data can be
monitored.
U64
U-Ai4/
USER function
code
USER P64
-32768 to
32767
When U-Ai4 is selected:
Universal Ai4(±16384/±10V) can be monitored.
If U-Ai is not defined, it acts as the user function code to read
and write data as universal data without affecting the inverter
operation.
H107
Light alarm target
definition 2
L-ALM 2
0000 to
1111
Select the alarm operation upon occurrence of a SX bus error
(
er4
) and toggle error (
arf
).
er4
and
arf
represent the number of hundreds and the
number of units, respectively.
0 in the corresponding decimal place: Alarm occurrence, 1:
Light alarm (
l-al
)
E10
|
E13
Select X11 - X14
function.
X11 ~ X14
FUNC
*2
Select the command when each of the X11 to X14 bits is 1.
To perform toggle monitoring with the X terminal bits, set
TGL1 and TGL2 for two of the terminals.
o160
*3
Function code
monitor (1) setting
0000h -
FFFFh
Only available when the standard format 2 is used. Sets the
function code continuously monitored by the function code
monitor (1) with 485No.
o161
*3
Function code
monitor (2) setting
0000h -
FFFFh
Only available when the standard format 2 is used. Sets the
function code continuously monitored by the function code
monitor (2) with 485No.
*1 For the details of o30 and o31, refer to "6.5.6.2 Protective operation function code".
*2 For the details, refer to "4.3 Function Code Details".
*3 For the details of o160 and o161, refer to "6.5.8.1 (4)
2
Function code monitor".
*4 For the details of user function code, refer to "6.5.5.1 Function code".
For other function codes, refer to Chapter 4.
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...