5-2
5.1.1 RS-485
common
specifications
Items Specifications
Protocol SX
protocol
(For FRENIC-VG Loader)
Modbus RTU
Fuji general-purpose inverter
protocol
Compliance
Loader dedicated protocol (Not
disclosed)
Modicon Modbus RTU-compliant
Fuji general-purpose inverter
protocol
Protocol
selection
Function code H40 = "1"
Function code H40 = "2"
Function code H40 = "0"
Messaging
system
Command message
RTU (Remote Terminal Unit) mode
only
ASCII mode not yet supported
Query/Broadcast message
Polling/Selecting/Broadcast
EIA RS-485
Electrical
specifications,
Transmission
speed
2,400 4,800 9,600 19,200 38,400 bps
Synchronization Asynchronous start-stop system (UART)
Transmission
mode
Half-duplex
Transmission
type
Direct link to inverter 1:N (1
≤
N
≤
31)
Transmission
character format
HEX
ASCII 7 bits or 8 bits
Data length
8 bits (fixed) (Note 3)
8 bits (fixed) (Note 2)
H35 data length setting
7 or 8 bits selectable
Stop bit
1 bit (fixed) (Note 3)
2 bits
(Note 2)
1 bit (Note 2)
H37 stop bit setting
1 or 2 bits selectable
Parity
Even (fixed) (Note 3)
None
Even
Odd
H36 parity setting
None, Even, or Odd selectable
Error checking
Sum-check
(1 byte BCC)
CRC-16
Generator polynomial:
X
16
+ X
15
+ X
2
+ 1
Sum-check
(2 byte BCC)
Logical station
selection
1-255; logical station
0; Broadcast
1-247; logical station
99; Broadcast (Note 1)
1-31; logical station
Frame length
Variable length
Variable length
Normal transmission:
16 bytes (fixed)
High-speed transmission:
8 or 12 bytes (fixed)
Max. transfer
data (1 message)
Write: 16 words
Read: 99 words
Write: 16 words
Read: 99 words
1 word
Disconnection
detection time
Communication disconnection time (Timeout) can be set with function code H38. Operates only during
operation through 485.
Cable length
Non-isolated: Max. 10 m
Isolated: Max. 500 m
* For isolation, use a commercially-available 485/485 isolating device (repeater), and a 485/232C isolated
converter.
* Inverters generate noise. Use a converter with superior noise resistance.
Recommended converters: KS-485PTI, KS-10PTI, USB-485I RJ45-T4P (System Sacom Sales Corporation)
(Note 1) For Broadcast, only communications command codes (S codes) are enabled. Other function codes are disabled.
(Note 2) With RTU protocol, H37 stop bit setting is not required because the stop bit is selected automatically in accordance with
the parity selection status (H36 parity setting).
(Note 3) With SX protocol, it is not necessary to change the H35-H37 settings because the data length, stop bit, and parity are fixed.
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...