6-110
6.5.9 Link
function
Refer to "6.3.9 Link function" of the T-Link interface.
When both of the SX bus interface card and T-Link interface card are installed, the link function
targets communication via the T-Link.
When only the SX bus interface card is installed and the monitoring format is selected, the link
function targets communication from the integrated RS-485.
6.5.10 Data transmission example
The following explains a data transmission example using the transmission format.
(1) Speed
setting
From MICREX-SX, give commands to run forward (FWD) at 750r/min.
(Condition: Function code U11 "SX transmission format selection"= 0, H30 "Link operation"=3,
maximum speed 1500 r/min, SX bus station address: 10)
Give S06 the forward running command (FWD: ON) and S01 the speed command.
%QW10.8 0 6 0 1
Function code S06, S01 selecting (link No. 06h, 01h)
%QW10.9 0 0 0 0
Selecting dummy data
%QW10.10 0 0 0 1
Function code S06 FWD=ON
%QW10.11 2 7 1 0
Function code S01 Speed setting 750/1500*20000=10000=2710(h)
↓
After acceleration completes
%IW10.6 2 7 1 0
Monitor the motor speed.
(2) Torque command monitor
Monitor the torque command value from MICREX-SX.
(Condition: Function code U11 "SX transmission format selection"= 0, SX bus station address: 10)
%QW10.14 1 0 0 0
Torque command monitor (link No. 10h)
%QW10.15 0 0 0 0
↓
After read completes
%IW10.0 1 0 0 0
When the link number requesting polling is returned to this area, reading is completed.
%IW10.1 0 0 0 0
Torque command value monitor data
%IW10.2 1 3 8 8
1388(h)
×
100(%)/ 10000 = 50(%)
%IW10.3 0 0 0 0
↓
%IW10.4 0 0 0 0
From the above, the torque command value is "50% of drive".
%IW10.5 0 0 0 0
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...