![Froling TURBOMAT TM 150 Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/froling/turbomat-tm-150/turbomat-tm-150_installation-instructions-manual_2338754060.webp)
Checking the door stop seal
❒ Open the door.
❒ Insert a sheet of paper at both the top and the bottom of the door stop between
the door and the boiler.
❒ Close the door.
❒ Try to pull out the sheets of paper.
➥ If the paper cannot be removed:
The door is sealed.
➥ If the paper can be removed:
The door is not sealed properly - Push the hinge toward the back.
⇨ See "Setting the combustion chamber door" [page 61]
Checking the door handle seal
❒ Open the door.
❒ Insert a sheet of paper at both the top and the bottom area at the side of the door
handle between the door and the boiler.
❒ Close the door.
❒ Try to pull out the sheets of paper.
➥ If the paper cannot be removed:
The door is sealed.
➥ If the paper can be removed:
The door is not sealed properly - Push the locking plate toward the back.
See also
2
Adjusting the combustion chamber doors [➙ 61]
4
Installation
Final installation steps
60
Fröling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com