Test data for pellets - emissions in [mg/MJ] (nominal load/partial load)
Carbon monoxide (CO)
mg/MJ
12 / 73
9 / 79
6 / 86
Nitrogen oxide (NOx)
mg/MJ
67 / 53
63 / 53
59 / 53
Organic hydrocarbons (OGC)
mg/MJ
<1 / <2
<1 / <2
<1 / 1.0
Dust
mg/MJ
9 / 10
8 / 11
6 / 13
Boiler efficiency
%
93.4 / 91.2
93.7 / 91.4
94.1 / 91.7
Test data for pellets - Emissions in [mg/m³]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/m³
13 / 107
11 / 117
9 / 127
Nitrogen oxide (NOx)
mg/m³
99 / 77
93 / 77
86 / 78
Organic hydrocarbons (OGC)
mg/m³
<2 / <2
<2 / <2
<2 / 1.5
Dust
mg/m³
13 / 14
11 / 16
8 / 19
Boiler efficiency
%
93.4 / 91.2
93.7 / 91.4
94.1 / 91.7
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Technology
3
Technical data
Installation Instructions | M0650314_en
15