4.5.23 Installing the combustion chamber overpressure and temperature sensors
40-50mm
❒ Screw in the spacer tube (1).
❒ Screw the brass bush (2) into the spacer tube (1).
❒ Push in the combustion chamber overpressure sensor (3) and slightly tighten the
retaining screw.
❒ Screw in the flanged pipe (4).
❒ Fit the counter flange (5).
❒ Insert the combustion chamber temperature sensor (6) so that it projects by ap‐
prox. 40 - 50 mm into the combustion chamber (7).
❒ Fix in position on the counterflange with the clamping screws. Only finger tighten
the screw.
Combustion chamber temperature sensor (6):
❒ Unscrew the connector box cover. Connect up the compensating line as follows:
- green wire to the terminal with the green dot
- white wire to the unmarked terminal
- shield not connected up.
❒ Fit the cover plate.
4
Installation
Installing the boiler
48
Fröling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com