3.3 Technical data
Description
TM
150
200
250
Nominal heat output
kW
150
199
250
Heat output range
kW
45 – 150
59 - 199
75 – 250
Electrical connection
400V / 50Hz / fuse protection C35A
Power consumption (pellets, wood chip)
W
545 / 657
578 / 659
612 / 660
Total weight including fittings
kg
3300
3820
3820
Weight - combustion chamber
1150
1290
1290
Weight - heat exchanger
1000
1280
1280
Heat exchanger water capacity
l
440
570
570
Water pressure drop (ΔT = 10 / 20 K)
mbar
36 / 12
55 / 18
74 / 25
Minimum boiler return temperature
°C
65
Maximum permitted operating temperature
°C
90
Permitted operating pressure
bar
3
Permitted fuel as per EN 14961
1)
Part 2: Wood pellets class A1 / D06
Part 4: Wood chips class A2 / P16A-P45A
Airborne sound level
dB(A)
< 70
1.Detailed information on the fuel is included in the operating instructions, in the section on “Permitted fuels”
150
200
250
Accredited Technical Inspection Association
TÜV
1)
TÜV
2) 3)
TÜV
1)
Test report no.
13-UW/Wels-
EX-033
14-U-187/SD
13-UW/Wels-
EX-308
Boiler class as per EN 303-5:2012
5
5
5
1.TÜV Austria Services GmbH, Geschäftsbereich Umweltschutz, Am Thalbach 15, A-4600 Thalheim/Wels
2.As per EN 303-5, Section 5.1.3 Type test: For a boiler from a range with the same constructional characteristics it is sufficient, if the ratio of nominal heat output from the largest to the
smallest boiler is ≤ 2:1, to perform the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in
the range, whose values have been determined depending on the rated heat output by interpolation, fulfil the requirements of the standard.
3.Values for the Type TM 200 are between those for the TM 150 and the TM 250 as certified in test reports 13-UW/Wels-EX-033 and 13-UW/Wels-EX-308.
Test data for wood chips - emissions in [mg/MJ] (nominal load/partial load)
Carbon monoxide (CO)
mg/MJ
2 / 50
5 / 54
8 / 58
Nitrogen oxide (NOx)
mg/MJ
82 / 79
87 / 78
92 / 76
Organic hydrocarbons (OGC)
mg/MJ
<1 / <2
<1 / <2
<1 / <2
Dust
mg/MJ
9 / 17
9 / 18
9 / 19
Boiler efficiency
%
91.6 / 90.6
92.4 / 91.1
93.3 / 91.6
Test data for wood chips - emissions in [mg/m³]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/m³
2 / 73
6 / 79
11 / 85
Nitrogen oxide (NOx)
mg/m³
120 / 116
127 / 114
135 / 111
Organic hydrocarbons (OGC)
mg/m³
<1 / <2
<1 / <2
<1 / <2
Dust
mg/m³
13 / 24
13 / 25
14 / 27
Boiler efficiency
%
91.6 / 90.6
92.4 / 91.1
93.3 / 91.6
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
3
Technology
Technical data
14