4.9 Final installation steps
4.9.1 Setting and testing the seal on the combustion chamber doors
Checking the settings of the door stop
❒ Close the door.
➥ A slight resistance must be felt when there is a gap of 2 - 3 cm:
Setting OK
➥ No resistance or only very slight resistance felt:
Setting must be corrected - Push the hinge toward the back.
⇨ See "Setting the combustion chamber door" [page 61]
➥ Resistance noticeable at a gap of >3 cm:
Setting must be corrected - Push the hinge toward the front.
⇨ See "Setting the combustion chamber door" [page 61]
Checking the settings of the door handle
❒ Close the door.
➥ The door can be closed with a normal amount of effort:
Setting OK
➥ The cannot be closed or can only be closed with great effort.
Push the locking plate toward the front.
⇨ See "Setting the combustion chamber door" [page 61]
Installation
4
Final installation steps
Installation Instructions | M0650314_en
59