![Froling TURBOMAT TM 150 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/froling/turbomat-tm-150/turbomat-tm-150_installation-instructions-manual_2338754041.webp)
❒ Fix the sensor (9) for the function monitor to the bracket (8).
❒ Attach the spring (10) at the bottom to the clamping bracket (11) and at the top to
the WOS lever (12).
❒ Set the sensor (9) for the function monitor as follows:
➥ Distance (13) between the sensor (9) and the WOS lever (12): 4-5mm
4.5.16 Installing the grate drive
Prepare the gear motor:
❒ Remove the shipping clamp from the gear motor.
❒ Fit the vent screw (supplied) to the highest point.
❒ Grease the shaft stub (1).
❒ Insert the seal (2) and the cover plate (3) onto the shaft.
❒ Fit the gear motor (4)
❒ Slide the key (5) into the groove and fit the shaft retainer (6).
❒ Fit the seal (2) and the blanking flange (7) on the opposite side to the gear motor
(4).
Installation
4
Installing the boiler
Installation Instructions | M0650314_en
41