16 Advanced functions
FLUXUS F401
16.10 Activation of a binary output as alarm output
113
UMFLUXUS_F401V2-1EN, 2020-06-12
16.10.1 Alarm properties
The switching condition, the holding behavior and the switching function of an alarm output
can be defined.
The following 3 scroll lists are displayed:
•
func
: switching condition
•
typ
: holding behavior
•
mode
: switching function
Press key
to select a scroll list in the upper line. Press key
to select a list item in
the lower line.
• Press ENTER to store the settings.
Tab. 16.1: Alarm properties
alarm property
setting
description
func
(switching condition)
MAX
The alarm will switch if the measured value exceeds
the upper limit.
MIN
The alarm will switch if the measured value falls below
the lower limit.
+→- -→+
The alarm will switch if the flow direction changes (sign
change of measured value).
QUANT.
The alarm will switch if totalizing is activated and the
totalizer reaches the limit.
ERROR
The alarm will switch if a measurement is not possible.
OFF
The alarm is switched off.
typ
(holding behavior)
NON-HOLD
If the switching condition is no longer true, the alarm
will return to the idle state after approx. 1 s.
HOLD
The alarm remains activated even if the switching
condition is no longer true.
mode
(switching function)
NO Cont.
The alarm is energized if the switching condition is true
and de-energized if idle.
NC Cont.
The alarm is de-energized if the switching condition is
true and energized if idle.
R1=FUNC<typ mode
Function:
MAX