AC Servo User's Manual
- 63 -
Pn305
JOG Speed
Setting Range
Setting Unit
Factory Setting
Setting Validation
0~6000 rpm
500
Immediately
Set the utility function Fn002 (JOG Mode Operation) to the reference value of servomotor speed.
The servomotor can be operated using only the panel operator without reference from the host controller.
Please note that the Forward Run Prohibited (P-OT) and Reverse Run Prohibited (N-OT) signals are invalid during JOG
mode operation.
4.1.2 Trial Operation for Servomotor without Load from Host Reference
Check that the servomotor move reference or I/O signals are correctly set from the host controller to the servo drive.
Also check the wiring and polarity between the host controller and servo drive, and the servo drive operation settings are
correct. This is the final check before connecting the servomotor to the machine.
(1)Servo ON Command from the Host
The following circuits are required: External input signal circuit or equivalent.
0V
+24V
/S-ON
P-OT
N-OT
V-REF
13
30
17
16
14
CN1
13
1
17
16
14
CN1
32
+24V
/S-ON
P-OT
N-OT
PULS
SIGN
Speed Control
(Standard Setting)
[Pn005=H.
□□0□]
Position Control
[Pn005=H.
□□1□]
0V
Speed
Position
Torque
Содержание pronet series
Страница 1: ...ProNet SeriesAC Servo User s Manual Version V2 10...
Страница 13: ...ProNet Series ACServoUser sManual 11 ProNet 1AD 1ED 2BD ProNet 02B ProNet 04B ProNet 08B...
Страница 21: ...ProNet Series ACServoUser sManual 19 ProNet 1AD 1ED 2BD ProNet 02B ProNet E 02B...
Страница 22: ...ProNet Series ACServoUser sManual 20 ProNet 04B ProNet E 04B ProNet 08B ProNet E 08B...
Страница 163: ...ProNet Series ACServoUser sManual 161 ProNet 75D 1AD 1ED 2BD Unit mm Air Flow Air Flow Air Flow...
Страница 193: ......