34
EN
Please make sure to observe the DIN EN 60335-1:2012-10 norm in respect to the leakage current.
This norm requires that the leakage current may not exceed the following limits at the normal
operating temperature:
“For stationary class I heating appliances - 0,75 mA or 0,75 mA per kW rated power input of the heating
appliance with a maximum of 5 mA, whichever is higher.”
The electricity supply must be protected with a residual-current-operated protective device (RCD)
with a rated fault current <30 mA. Please make sure that no other electrical appliances are protect-
ed with this RCD device.
The applicable international, national and local legal norms and requirements (e.g. VDE, EU regula-
tions) in their currently valid version should be observed. All installation and testing works should
be carried out by a licensed and appropriately qualified electrician with the respect to the men-
tioned norms and codes (e.g. VDE 0100 part 701). All works may be only carried out when the
steam generator is completely disconnected from power.
8.11 Leakage current