Commissioning
Proline t-mass 65 PROFIBUS DP
64
6.6.4
Configuration examples with Simatic S7 HW-Konfig
Example 1
a0005497
Fig. 35:
Complete configuration using the t-mass 65 GSD file
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS Master (class 1):
Slot
sequence
Module
Byte
length
input
data
Byte
length
output
data
Description
1
AI
5
-
Analog Input function block 1
Output variable
→
mass flow (factory setting)
2
AI
5
-
Analog Input function block 1
Output variable
→
corr. volume flow (factory setting)
3
AI
5
-
Analog Input function block 1
Output variable
→
temperature (factory setting)
4
SETTOT
_MODETOT
_TOTAL
5
2
Totalizer function block 1
TOTAL
→
output variable = totalized mass flow (factory setting)
SETTOT
→
totalizer control
MODETOT
→
totalizer configuration
5
SETTOT
_MODETOT
_TOTAL
5
2
Totalizer function block 2
TOTAL
→
output variable = totalized mass flow (factory setting)
SETTOT
→
totalizer control
MODETOT
→
totalizer configuration
6
DISPLAY
_VALUE
-
5
Value for local display
7
CONTROL
_BLOCK
-
1
Control of device functions
8
PRESSURE
_VALUE
-
5
Process pressure
Содержание Proline t-mass 65 PROFIBUS DP