Proline t-mass 65 PROFIBUS DP
Installation
15
a0005113
Fig. 5:
The figure above illustrates the minimum recommended inlet und outlet runs expressed in multiples of the pipe
diameter.
1 = Reduction
2 = Expansion
3 = 90° elbow or T-piece
4 = 2 x 90° elbow
5 = 2 x 90° elbow, 3-dimensional
6 = Control valve (where possible a modulating control valve should be mounted downstream of a flowmeter)
a = Inlet run
b= Outlet run
!
Note!
Wherever possible mount any control and butterfly shut off valves downstream of the flowmeter.
15 x DN
2 x DN
a
1
b
3
a
b
15 x DN
2 x DN
5
a
b
20 x DN
2 x DN
4
a
b
35 x DN
2 x DN
6
a
b
50 x DN
2 x DN
2
a
b
15 x DN
2 x DN
a
b
20 x DN
5 x DN
a
b
20 x DN
5 x DN
a
b
20 x DN
5 x DN
a
b
25 x DN
5 x DN
a
b
40 x DN
5 x DN
a
b
50 x DN
5 x DN