Commissioning
Proline t-mass 65 PROFIBUS DP
50
6.3.2
Quick Setup “Communication”
To establish cyclic data transfer, various arrangements between the PROFIBUS Master (class 1)
and the slave are required which have to be taken into consideration when configuring various
functions. These functions can be configured quickly and easily by means of the Communication
Quick Setup.
A0005459-EN
Fig. 32:
Quick Setup Communication
QUICK SETUP - COMMUNICATION
Use the
O
or
S
key at the prompt “QS-COMMUNICATION NO” and the device access code
entry appears. Enter the device access code “65” and press
F
; programming is enabled.
The prompt “QS-COMMUNICATION NO” appears. Use the
O
or
S
key to change “NO” to “YES”
and press
F
.
FIELDBUS ADDRESS
Use the
O
or
S
key to enter the device address (0...126) and continue with
F
.
SELECTION GSD
Use the
O
or
S
key to select the operating mode (GSD file) which should be used for cyclic
communication with the PROFIBUS Master (class 1) and continue with
F
.
• MANUFACT. SPEC. (factory setting): The measuring device is operated with complete device
functionality.
• PROFILE-GSD The measuring device is operated in the PROFIBUS Profile mode.
!
Note!
For PROFIBUS network configuration, make sure that the right device master file (GSD file) of the
measuring device is used for the selected operating mode.
UNIT TO BUS
If this function is executed, the measured variables (AI modules) transmitted cyclically are
transmitted to the PROFIBUS Master (class 1) with the system unit configured in the
measuring device.
Other Quick Setup?
To execute the Quick Setup Commission or back to the Quick Setup function group.
+
+
E
Esc
E
+
-
XXX.XXX.XX
+
E
HOME
POSITION
Setup
Communication
Quick Setup
Off
Set unit
Unit to bus
QS Commission
No
Other Quick Setup?
Fieldbus
Address
Selection
GSD
QS Commission