Installation
Proline t-mass 65 PROFIBUS DP
26
Mounted directly on the wall
1.
Drill the holes as illustrated in the diagram.
2.
Remove the cover of the connection compartment (a).
3.
Push the two securing screws (b) through the appropriate bores (c) in the housing.
– Securing screws (M6): max. Ø 6.5 mm (0.25 inch)
– Screw head: max. Ø 10.5 mm (0.4 inch)
4.
Secure the transmitter housing to the wall as indicated.
5.
Screw the cover of the connection compartment (a) firmly onto the housing.
a0001130-ae
Fig. 17:
Mounted directly on the wall
Installation in control panel
1.
Prepare the opening in the panel as illustrated in the diagram.
2.
Slide the housing into the opening in the panel from the front.
3.
Screw the fasteners onto the wall-mount housing.
4.
Screw threaded rods into holders and tighten until
the housing is solidly seated on the panel wall. Afterwards, tighten the locking nuts.
Additional support is not necessary.
a0001131-ae
Fig. 18:
Panel installation (wall-mount housing)
a
b
c
c
90 (3.54)
35 (1.38)
192 (7.56)
81.5
(3.2)
mm (inch)
245 (9.65)
~110 (~4.33)
210 (8.27)
+0.5 (+0.019)