Table 2-1: Troubleshooting
(continued)
Error
Recommended action(s)
Sound velocity is outside defined
limits
The meter's measured average sound velocity is outside the
defined limits.
•
Verify that all chords are measuring the same Speed of
Sound within about 0.15%. Look for alarms that indicate
transducer problems and resolve any of these issues. This
could include failing transducers, debris buildup on
transducers, or incorrectly entered path lengths in the
configuration.
•
If the chords agree, adjust the
SSMin
or
SSMax
using the
Field Setup Wizard in MeterLink so the meter's average
speed of sound falls within these limits (consult with an
Emerson Flow service representative before changing these
parameters).
•
Collect a Maintenance log using MeterLink and contact your
Emerson Flow service representative.
Waveform contains an excessive
amount of noise
Use the MeterLink
Meter
→
Signal Analyzer
to increase the
StackSize
until noise level decreases (settings can be 1 (none)
2, 4, 8, or 16). If increasing the
StackSize
is not successful, try
turning on the filter or consult with Emerson Customer Support
if you are unsure of how stacking a signal can affect the meter's
operation.
(1)
Note: The latest version of the Rosemount Liquid Ultrasonic Meter firmware is available to
download from
https://www.emerson.com/en-us/catalog/rosemount-sku-meterlink-
2.2.1
Meter monitoring maintenance
Run MeterLink and open the Meter Monitor (Summary) to view the current health status of
your meter.
The Monitor (Summary) includes the direction of flow measurement, velocity rate, units of
measurement, uncorrected or corrected flow (if applicable for your meter) and a bar graph
for a visual comparison between the velocities for each chord.
Troubleshooting
Maintenance and Troubleshooting Manual
April 2022
00809-0100-3812
24
Emerson.com/Rosemount
Содержание Rosemount 3812
Страница 4: ...Contents Maintenance and Troubleshooting Manual April 2022 00809 0100 3812 4 Emerson com Rosemount ...
Страница 12: ...Routine Maintenance Maintenance and Troubleshooting Manual April 2022 00809 0100 3812 12 Emerson com Rosemount ...
Страница 36: ...Troubleshooting Maintenance and Troubleshooting Manual April 2022 00809 0100 3812 36 Emerson com Rosemount ...
Страница 126: ...Meter maintenance Maintenance and Troubleshooting Manual April 2022 00809 0100 3812 126 Emerson com Rosemount ...
Страница 130: ...Engineering drawings Maintenance and Troubleshooting Manual April 2022 00809 0100 3812 130 Emerson com Rosemount ...