User Manual
Chapter 3
GFK-1742F
Jan 2020
Installing and Wiring the DSM314
86
Single Ended 5v Inputs/Outputs
Circuit
Identifier
Digital Servo
Axis 1, 2
Circuit
Function
Analog Servo
Axis 1-4 and
Aux Axis 2-4
Circuit Function
Signal Name
(X = A, B, C, or
D Connector)
Faceplate
Pin
Auxiliary
Terminal
Board
Servo
Terminal
Board
IO5
0V
Servo PWM /
Alarm
0v
Strobe 1 Input
0v
IO5_X / IN5_X
0V_X
9
27
9
27
N/C
N/C
IO6
0V
Servo PWM /
Alarm
0v
Strobe 2 Input
0v
IO6_X / IN6_X
0V_X
10
28
10
28
N/C
N/C
IO7
0V
Servo PWM /
Alarm
0v
Not Used
0v
IO7_X / IN7_X
0V_X
11
29
11
29
N/C
N/C
IO8
0V
Servo ENBL /
Alarm
0v
Not Used
0v
IO8_X / IN8_X
0V_X
12
30
12
30
N/C
N/C
I/O Type:
Single Ended 5v Inputs / Outputs
Circuit Type:
Sink (4.7K ohm pull-up to in5v)
Input Impedance:
4.7K ohms to in5v
Maximum Input Voltage:
-1.0 v, +7.0v
Logic 0 Input Threshold:
+0.8 v max
Logic 1 Input Threshold:
+2.4 v min
Input Filtering:
10 microseconds typical
Output Sink Current
10 mA max
On State Output Voltage
+0.5v at 10 mA
Strobe Response:
Minimum Pulse Width: 10 microseconds. Position
Capture Accuracy: +/- 2 counts with an additional 10
microseconds of variance
Note:
For digital servos, these points act as the PWM / ENBL outputs and Alarm inputs. For Analog Servos
and Aux axes, these points are input only. The listed 0v pins should be normally used for the signal
return.