Updating Firmware in the DSM314
460
8.
When the download is complete, the PC loader will instruct you to power cycle your
module. At this time, power cycle the module. If the module is installed in an
expansion or remote rack, it is necessary to also power-cycle the main rack.
9.
Label the unit with the installed firmware version. If the firmware is Beta or an
Engineering Release, indicate so on the label.
F-3
Restarting an Interrupted Firmware Upgrade
A.
Connect all cables as described in step 4 of the procedure above.
B.
Power cycle the rack containing the module. If a partial or erroneous download was
performed, the module will power up with the STAT and CFG LED’s on the module
flashing in unison.
C.
If you are still running the PC Loader or Winloader program on your PC, skip to step
D below; otherwise, follow steps 5 and 6 above.
D.
Follow step 7 above. Note that you will automatically be placed in BOOT MODE. E.
Follow steps 9 through 12 above.
E.
If the update still fails, repeat the process with a lower baud rate.
F.
Label your unit with the installed firmware version.