User Manual
Chapter 2
GFK-1742F
Jan 2020
System Overview
32
4.
Connect the 220 VAC Power Cable (K3) to the
β
Series Digital Amplifier
The AC power cable is a user-supplied cable that connects to CX11
–
1 on the face of the
Series amplifier. The connector for the amplifier end of this cable is part of kit ZA06B-6093-
K305 supplied with each amplifier package. See the Servo Product Specification Guide, GFH-
001, for more detailed information.
An AC line filter will reduce the harmonic noise effect to the power supply; its use is
recommended. A line filter is not needed if an isolation transformer or separate power
transformer is used. Two or more amplifiers may be connected to one AC line filter or
transformer if its power capacity is not exceeded. Figure 15 shows how to connect the
amplifier to the line filter.
Figure 15: Connecting the
Series Servo Amplifier to the Line Filter and Power Source
Note:
You must supply the cable for the connection between the line filter and the power source. Use 4-
conductor, 600V, 60°C (140°F), UL or CSA approved cable between the line filter and the servo
amplifier. The gauge of wire used for connecting the line filter to the power source must be sized,
based on the size of the circuit breaker between the power source and the line filter and the
number of servos connected to the line filter. The power connectors and terminals are supplied as
part of the amplifier package.