User Manual
Chapter 3
GFK-1742F
Jan 2020
Installing and Wiring the DSM314
91
Single Ended +/- 10v Analog Output
Circuit
Identifier
Analog Servo Axis
1-4 Circuit Function
Digital Servo Axis
1,2 and Aux Axis 2-
4 Circuit Function
Signal Name
(X = A, B, C, or
D Connector)
Faceplate
Pin
Auxiliary
Terminal
Board
Servo
Terminal
Board
AOUT1
Analog Servo Velocity
Command or Analog
Servo Torque
Command
Faceplate Analog Out
AOUT_X
6
6
4
ACOM
Analog Out Com
Analog Out Com
ACOM_X
24
24
12
I/O Type:
Single Ended Analog
Output Circuit Type:
Op Amp Voltage Follower Output
Load Impedance:
2K ohms minimum
Output Current:
5 mA max
Resolution:
13 bits
Linearity:
13 bits
Output Offset Voltage:
+/- 500 microvolts max
Force D/A Gain Factor:
+/- 10.0v = +/- 32000 counts
Gain Accuracy:
+/- 1.0 %
Force Analog Output Update Rate: Host controller sweep rate when used by Force
Analog Output %AQ command.
250 microseconds when used as Digital Servo tuning
output.
Note:
Since this is a single ended output, it should normally drive a user device with a differential input
to prevent common mode noise problems. The positive differential input should be connected to
AOUT and the negative differential input to ACOM.
The Select Analog Output Mode %AQ command can be used to select the source for the analog