User Manual
Chapter 3
GFK-1742F
Jan 2020
Installing and Wiring the DSM314
61
3.3.4
Auxiliary Terminal Board - IC693ACC336
Description and Mounting Dimensions
The IC693ACC336 Auxiliary Terminal Board is used to connect the DSM314 to Analog Servo
Axes and auxiliary devices such as Incremental Quadrature Encoders, Strobe detectors and
external switches. The board contains one 36 pin connector, labeled DSM. A cable
IC693CBL324 (1 meter) or IC693CBL325 (3 meters) connects from the DSM connector (PL2)
to the DSM314 faceplate.
Thirty-eight screw terminals are provided on the Auxiliary Terminal Board for connections
to user devices. These screw terminals have the same pin labels as the 36-pin DSM314
faceplate connector. For detailed connection information, refer to “Analog Servo Axis 1
-4
Circuit and Pin As
signments “
on page 71.
The maximum voltage that should be applied to I/O terminals 16-18 and 34-36 is 30 VDC.
The maximum voltage for any other input terminal is 5 VDC.
Six 130V MOVs are installed between selected I/O points and the shield (frame ground) for
noise suppression. The I/O terminal points so connected are 16, 17, 18, 34, 35, and 36.
The I/O terminals support a wire gauge of 14-28 AWG. Maximum screw torque that may be
applied is 5 inch-pounds.
Note:
Two of the screw terminals are labeled S for Shield. A short earth ground wire should be connected
from one of the S terminals directly to a panel earth ground. The cable shields for any shielded
cables from user devices should connect to either of the S terminals.
Figure 37: IC693ACC336 Terminal Board Mounting Dimensions