Connect 24V DC Cable (K12) to the
Series Digital Servo Amplifier
A connector for the external 24 VDC supply is included with the amplifier package as a part
of kit ZA06B-6093-K305 and should be connected to CX11-4. The other end of the cable
must be connected to a 24VDC source capable of supplying at least 450 milliamps of current
for each
Series amplifier. The Emerson IC690PWR024 power supply is recommended. Do
not apply power at this time.
7.
Connect Cable K8
–
Jumper or External Regeneration Resistor to the
Series Digital
Servo Amplifier
Without External Regeneration Resistor (Using a Jumper)
If you do not have an external regeneration resistor, you must leave the connections on
CX11-2 (DCP and DCC) open. However, you must jumper the CX11-6 (TH1 and TH2)
terminals, shown in the figure below. (This jumper completes the circuit that would
otherwise be completed by the normally closed thermal over-temperature switch in the
external regeneration resistor unit.) If you do not have this jumper installed, the amplifier
will not function. The jumper and its connector are included as a part of the connector kit
ZA06B-6093-K305 that is shipped with each amplifier package.