4 Technical features
4.5 Address setting
42
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
4.5.5
Address setting via BootP-mode
The address setting is carried out by a BootP-server in the network after the start-up of the
gateway.
In order to activate the BootP-mode, the DIP-switch "MODE" is set to "ON", the address swit-
ches 2
0
to 2
7
to address "2" (see Table 6: Combinations for the address-switch settings,
LED-behavior
During it’s start-up, the module waits for the address setting via the DHCP-/BootP-server. This
is indicated by the red flashing "MS" LED. The LED begins to flash green, as soon as the
address setting via the server is completed. The station is ready for communication.
Figure 26:
BootP
Note
The subnet mask as well as the default IP address mask assigned to the gateway by
the BootP-server are stored in the gateway’s non-volatile EEPROM.
If the gateway is subsequently switched to another adress-mode, the settings car-
ried out via BootP (IP address, subnet mask, etc.) will be taken from the module’s
EEPROM.
Attention
After every change of the address-mode, a voltage reset must be carried out.
Содержание XN-GW Series
Страница 1: ...09 2011 MN05002007Z EN User Manual XI ON XNE GWBR 2ETH IP Gateway...
Страница 8: ...Table of contents 8 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com 10 Index 205...
Страница 12: ...1 About this manual 1 3 Overview 12 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 28: ...3 EtherNet IP 3 1 System description 28 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 184: ...7 Guidelines for station planning 7 7 Firmware download 184 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 204: ...9 Appendix 9 3 Glossary 204 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...