5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
112
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
134
(86h)
Direction input B
G/S
BOOL
States if the direction input B will be
inverted.
Direction input B:
– FALSE: normal
– TRUE: inverted
135
(87h)
Group diagnostics G/S
BOOL
Defines if the group diagnostic will be trans-
mitted to the gateway or not.
Group diagnostic:
– FALSE: release
– TRUE: block
136
(88h)
On I/O connec-
tion fault
G/S
ENUM
USINT
Defines the behavior of the module in the
cased of an I/O Connection Fault of the
gateway.
Behavior by I/O Connection Fault (para-
meter name of the counter: CPU/master
STOP):
– 0: turn off DO1
– 1: proceed with operating mode
– 2: DO1 switch to Fault Value
– 3: DO1 hold last value
– 4 to 255:reserved
Table 55:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
Содержание XN-GW Series
Страница 1: ...09 2011 MN05002007Z EN User Manual XI ON XNE GWBR 2ETH IP Gateway...
Страница 8: ...Table of contents 8 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com 10 Index 205...
Страница 12: ...1 About this manual 1 3 Overview 12 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 28: ...3 EtherNet IP 3 1 System description 28 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 184: ...7 Guidelines for station planning 7 7 Firmware download 184 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 204: ...9 Appendix 9 3 Glossary 204 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...