5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
108
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
112
(70h)
Counter diag
G
WORD
MSRM:
Bit 8:
0 = ok
1 = short- circuit/open circuit
Bit 9:
0 = ok
1 = short-circuit in sensor power supply
24 VDC
Bit 10:
0 = ok
1 = sensor pulse wrong
Bit 11:
0 = ok
1 = integration time wrong
Bit 12:
0 = ok
1 = upper limit wrong
Bit 13:
0 = ok
1 = power limit wrong
Bit 14:
0 = ok
1 = measurement operating mode
wrong
Bit 15:
0 = measurement Mode NOT active
1 = measurement Mode active
113
(71h)
Basic mode
G/S
ENUM
USINT
Defines the operating mode of the counter
module; hence, it must be written first. The
definition of the operating mode in this attri-
bute is the prerequisite for all further
Instances and attributes in this class.
Operating mode (basic mode):
– 0: CNT: continuous count
– 1: CNT: single-action count
– 2: CNT: periodical count
– 3: MSRM: frequency measurement
– 4: MSRM: revolutions measurement
– 5: MSRM: period duration measurement
– 6 to 255: reserved
Table 55:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
Содержание XN-GW Series
Страница 1: ...09 2011 MN05002007Z EN User Manual XI ON XNE GWBR 2ETH IP Gateway...
Страница 8: ...Table of contents 8 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com 10 Index 205...
Страница 12: ...1 About this manual 1 3 Overview 12 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 28: ...3 EtherNet IP 3 1 System description 28 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 184: ...7 Guidelines for station planning 7 7 Firmware download 184 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 204: ...9 Appendix 9 3 Glossary 204 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...