6 Application example: XNE gateway with an Allen Bradley PLC
6.3 Changing the IP address of a PC/ network interface card
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
159
6.3.5
Address setting via DHCP-mode
In this application example, the IP address is set via DHCP using the software tool
"BootP/DHCP-Server" version 2.3.2.0 from Rockwell Automation.
Addresses in the range from 1 to 254 can be allocated. The addresses 0 and 255 are reserved
for broadcast messages in the subnet.
After having been connected to the network, the XI/ON sends DHCP requests to the server
using its MAC-ID.
Figure 44:
BootP-Server
from Rockwell
Automation
Note
In order to activate the DHCP-mode, the DIP-switch "MODE" is set to "ON", the
address-switches 2
0
to 2
7
to address "1".
Figure 45:
DHCP-request
of XI/ON gate-