6 Application example: XNE gateway with an Allen Bradley PLC
6.5 Configuration of the network in "RSLogiX 5000"
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
165
For the Assembly Instances 101 and 102, the Connection Parameters (input and output size
= 256 Byte each) are static and have to be set as follows:
In the "Connection" tab set the "Requested Packet Interval" (RPI) to 10 ms, which normally
should be the default setting. For XI/ON, the successfully tested RPI range is 5 and higher.
Figure 57:
Configuration of
XI/ON gateway
Note
If the variable Assembly Instances 103 and 104 (see page 63) are used, the
Connection Parameters have to be set according to the actual station configuration
which means, the in- and output sizes have to match the sizes definitely required by
the station. This required in- and output size (2 to max. 496 Byte) can be read out
using Assembly Class (0×04), Instance 0×67, Attr. 0×04 and Assembly Class (0×04),
Instance 0×68, Attr. 0×04.
Figure 58:
Set connection
options for
XI/ON
Содержание XN-GW Series
Страница 1: ...09 2011 MN05002007Z EN User Manual XI ON XNE GWBR 2ETH IP Gateway...
Страница 8: ...Table of contents 8 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com 10 Index 205...
Страница 12: ...1 About this manual 1 3 Overview 12 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 28: ...3 EtherNet IP 3 1 System description 28 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 184: ...7 Guidelines for station planning 7 7 Firmware download 184 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 204: ...9 Appendix 9 3 Glossary 204 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...