5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
107
110
(6Eh)
Module regis-
tered index
G
ENUM
USINT
Contains the index numbers specified in all
the module lists.
111
(6Fh)
Number of
supported chan-
nels
G
USINT
States the number of analog input channels
supported by this module Instance.
112
(70h)
Counter diag
G
WORD
Contains the diagnostic data of the counter
module. Bits 0 to 7 apply to the counter
mode (CNT); bits 8 to 15 the counter mode
(MSRM).
CNT:
Bit 0:
0 = ok
1 = short-circuit/open circuit
Bit 1:
0 = ok
1 = short-circuit in sensor power supply
24 VDC
Bit 2:
0 = ok
1 = upper limit wrong
Bit 3:
0 = ok
1 = lower limit wrong
Bit 4:
0 = ok
1 = it is not permitted to invert the level
of the digital input when using the latch
retrigger function
Bit 5:
0 = ok
1 = main count direction wrong
Bit 6:
0 = ok
1 = counter operating mode wrong
Bit 7:
0 = CNT Mode NOT active
1 = CNT Mode active
Table 55:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
Содержание XN-GW Series
Страница 1: ...09 2011 MN05002007Z EN User Manual XI ON XNE GWBR 2ETH IP Gateway...
Страница 8: ...Table of contents 8 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com 10 Index 205...
Страница 12: ...1 About this manual 1 3 Overview 12 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 28: ...3 EtherNet IP 3 1 System description 28 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 184: ...7 Guidelines for station planning 7 7 Firmware download 184 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 204: ...9 Appendix 9 3 Glossary 204 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...