4 Technical features
4.3 Technical data
32
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
Residual ripple
according to IEC/EN 61131-2
Voltage anomalies
according to IEC/EN 61131-2
Connection technology
Push-in tension clamp terminals,
LSF from Weidmueller
Physical interfaces
Fieldbus
Protocol
Ethernet
Transmission rate
10/100 MBit
Passive fibre-optic-adapters can be
connected
current consumption max. 100 mA
Fieldbus connection
RJ45-female connector, RJ45-male connector
Fieldbus shielding connection
via Ethernet cable
Address setting
via DIP-switches (2
0
to 2
7
)
Service interface
mini USB
Isolation voltages
U
SYS
to service interface USB
-
U
L
, U
SYS
to Ethernet
500 V
rms
ETH1 to ETH2
500 V
rms
Ambient conditions
Ambient temperature
Operating temperature
0 to +55 °C / 32 to 131 °F
Storage temperature
-25 to +85 °C / 13 to 185 °F
Relative humidity according to
IEC/EN 60068-2-30
5 to 95 % (indoor), Level RH-2, no condensa-
tion (storage at 45 °C, no function test)
Climatic tests
according to IEC/EN 61131-2
Resistance to vibration according to IEC/EN 60068-2-6
10 to 57 Hz, constant
amplitude 0.075 mm / 0.003 inch, 1g
Yes
57 to 150 Hz, constant
acceleration 1 g
Yes
Mode of vibration
Frequency sweeps with a change in speed of
1 Octave/min
Period of oscillation
20 frequency sweeps per axis of coordinate
Содержание XN-GW Series
Страница 1: ...09 2011 MN05002007Z EN User Manual XI ON XNE GWBR 2ETH IP Gateway...
Страница 8: ...Table of contents 8 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com 10 Index 205...
Страница 12: ...1 About this manual 1 3 Overview 12 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 28: ...3 EtherNet IP 3 1 System description 28 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...
Страница 184: ...7 Guidelines for station planning 7 7 Firmware download 184 XI ON XNE GWBR 2ETH IP 09 2011 MN05002007Z EN www eaton com...