
WRM-10P S2 USER’S MANUAL REV 1.0
40
c.
The following screen will be displayed:
NOTE
•
The interval value is the interval at which the WRM-10P S2 takes current
measurements (1 - 20 mSecs).
•
The threshold value determines the tolerance threshold for changes in the
voltage measurements (1 - 5). This value is multiplied by 0.36V to
determine the threshold value for voltage spikes.
1.
CONTINUE
Press the
[1]
key (
CONTINUE
) if you do not want to make any changes to the test
parameters.
Continue to step d.
2.
EDIT SETTINGS
Press the
[2]
key (
EDIT SETTINGS
) if you would like to change the test
parameters.
The following screen will be displayed:
Press the
[
]
or
[
]
key to increase or decrease the time interval by 1 mSec
increments, respectively. Press the
[ENTER]
key.
The following screen will be displayed:
Press the
[
]
or
[
]
key to increment or decrement the threshold level,
respectively. Press the
[ENTER]
key and
continue to step d
.
THRESHOLD LEVEL
( 1-5): 2
↑↓
to Adjust
"ENTER" to Accept
TIME INTERVAL
( 1-20): 5 mSec
↑↓
to Adjust
"ENTER" to Accept
TRANSIENT FILTER
INTERVAL: 5 mSecs
THRESHOLD: 2
1. CONTINUE
2. EDIT SETTINGS
Содержание Vanguard Instruments WRM-10P S2
Страница 28: ...WRM 10P S2 USER S MANUAL REV 1 0 24 Figure 8 Typical V1 and V2 Test Report Printout with Multiple Readings ...
Страница 35: ...REV 1 0 WRM 10P S2 USER S MANUAL 31 Figure 9 Typical LTC Voltage Regulator Test Report Printout ...
Страница 47: ...REV 1 0 WRM 10P S2 USER S MANUAL 43 Figure 11 Typical Transient Test Report ...
Страница 65: ...REV 1 0 WRM 10P S2 USER S MANUAL 61 Figure 12 Typical Internal Test Record Directory Printout ...
Страница 67: ...REV 1 0 WRM 10P S2 USER S MANUAL 63 Figure 13 Typical USB Flash Drive Test Record Directory Printout ...