WRM-10P S2 USER’S MANUAL REV 1.0
16
3.6
Performing a Resistance Test
a.
Start from the “START-UP” menu:
Press the
[1]
key (
RUN TEST
).
b.
The following screen will be displayed:
Press the
[1]
key (
V1 & V2 TEST
) if you would like to perform a V1 & V2 test.
Press the
[2]
key (
V1 ONLY TEST
) if you would like to perform a V1 test only.
For this example, we will perform a V1 Only Test by pressing the
[2]
key.
Please see section 3.8 for information about performing special tests.
NOTE
The WRM-10P S2's test current is 10 Amps.
c.
The following menu will be displayed:
Press the
[2]
key (
NO
).
LTC or VTG REGULATOR?
1. YES
2. NO
1.V1 & V2 TEST
2.V1 ONLY TEST
3.SPECIAL TEST V1, V2
4.SPECIAL TEST V1
5.TRANSIENT TEST
1.RUN TEST
2.TEST RECORDS
3.DIAGNOSTICS
4.SETUP
08/30/17
08:51:56