WRM-10P S2 USER’S MANUAL REV 1.0
34
You can increase the Tk value by 0.5
°
C increments by pressing the
[
]
key.
You can decrease the Tk value by 0.5
°
C increments by pressing the
[
]
key.
Press the
[ENTER]
key to confirm the temperature setting.
Continue to step f.
2.
NO
Press the
[2]
key (NO) if you do NOT wish to convert readings to standard
temperature.
Continue to step h.
f.
The following screen will be displayed:
Use the
[
]
and
[
]
keys to adjust the D.U.T. (Device Under Test) temperature.
Press the
[ENTER]
key to confirm the D.U.T. temperature setting.
g.
The following screen will be displayed:
Use the
[
]
and
[
]
keys to adjust the reference temperature.
Press the
[ENTER]
key to confirm the reference temperature setting.
REFERENCE TEMP:
75.0
°
C 167.0
°
F
↑↓
to Adjust Temp,
"ENTER" to Accept
D.U.T. TEMP:
25.0
°
C 77.0
°
F
↑↓
to Adjust Temp,
"ENTER" to Accept
T
K
:
230.0
°
C
↑↓
to Adjust Temp,
"ENTER" to Accept