Ch12 Descriptions of Parameter Settings
| VFD-ED
12-71
Motor Rated Current
Control Mode
FOCPM
Unit:
Amp
Default: #.##
Settings
(40–120%) * Pr.00-01 Amps
Sets according to the motor rated current as indicated on the motor nameplate. The default is 90% of the
rated current.
Example: Suppose the rated current for 7.5 HP (5.5 kW) models is 25 A and the default is 22.5 A. In this
case, the current range is from 10 A (25 * 40%) to 30 A (25 * 120%).
Motor Rated Power
Control Mode
FOCPM
Default:
#.##
Settings
0.00–655.35 kW
Sets the motor rated power. The default is the power of the drive.
Motor Rated Speed (rpm)
Control Mode
FOCPM
Default:
1710
Settings
0–65535 rpm
Sets the motor rated speed according to the motor nameplate.
Number of Motor Poles
Control Mode
FOCPM
Default:
4
Settings
2–96
Sets the number of motor poles (must be an even number).
Motor Rs
Control Mode
FOCPM
Default:
0.000
Settings
0.000–65.535
Ω
Motor Ld
Motor Lq
Control Mode
FOCPM
Default:
0.0
Settings
0.0–6553.5 mH
Back Electromotive Force
Control Mode
FOCPM
Default:
0.0
Settings
0.0–6553.5 Vrms
Sets the back electromotive force (phase-phase RMS value) when the motor is operated at the rated
speed.
You can get the RMS value by setting Pr.08-00 = 2 (Motor Auto-tuning).
Offset Angle between Magnetic Pole and PG Origin
Control Mode
FOCPM
Default:
360.0
Settings
0.0–360.0°
The offset angle between the magnetic pole and PG origin (measured by auto-tuning).
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...