06 Optional Accessories | VFD-ED
6-7
6-2 Non-fuse Circuit Breaker
Comply with the UL standard: Per UL 508, paragraph 45.8.4, part a. The rated current of a breaker
shall be two to four times the maximum rated input current of the AC motor drive.
One-phase/Three-phase
Three-phase
Model
Recommended non-fuse
breaker (A)
Model
Recommended non-fuse
breaker (A)
VFD022ED21S* 50
VFD040ED43S
30
VFD037ED21S* 75
VFD055ED43S
35
VFD040ED23S 40
VFD075ED43S 40
VFD055ED23S 50
VFD110ED43S 50
VFD075ED23S 60
VFD150ED43S 60
VFD110ED23S 100
VFD185ED43S 75
VFD150ED23S 125
VFD220ED43S 100
VFD185ED23S 150
VFD300ED43S 125
VFD220ED23S 175
VFD370ED43S 150
VFD300ED23S 250
VFD450ED43S 200
VFD370ED23S 300
VFD550ED43S 250
VFD750ED43S
350
* VFD022ED21S and VFD037ED21S are one-phase models.
6-3 Fuse Specification Chart
Fuse specifications lower than the table below are allowed.
Model
Input Current (A)
Line Fuse
I (A)
Bussmann P/N
VFD022ED21S 26
60
JJN-60
VFD037ED21S 37
90
JJN-90
VFD040ED23S 20
50
JJN-50
VFD055ED23S 23
60
JJN-60
VFD075ED23S 30
80
JJN-80
VFD110ED23S 47
125
JJN-125
VFD150ED23S 56
150
JJN-150
VFD185ED23S 73
175
JJN-175
VFD220ED23S 90
225
JJN-225
VFD300ED23S 132
300
JJN-300
VFD370ED23S 161
400
JJN-400
VFD040ED43S 11.5
35
JJS-35
VFD055ED43S 14
40
JJS-40
VFD075ED43S 17
45
JJS-45
VFD110ED43S 24
60
JJS-60
VFD150ED43S 30
80
JJS-80
VFD185ED43S 37
90
JJS-90
VFD220ED43S 47
110
JJS-110
VFD300ED43S 58
150
JJS-150
VFD370ED43S 80
200
JJS-200
VFD450ED43S 100
250
JJS-250
VFD550ED43S 128
300
JJS-300
VFD750ED43S 165
400
JJS-400
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...