Ch12 Descriptions of Parameter Settings
| VFD-ED
12-22
41
Magnetic contactor detection
This terminal is for the magnetic contactor feedback signal
ON/OFF.
When the motor drive receives a RUN command, it enables the
corresponding output terminal (setting 15) after Pr.02-31 time. It
checks if this function is enabled in the detection time
(Pr.02-36). If NOT, the magnetic contactor error occurs and
error code “MCF” displays.
42
Mechanical brake 1
When the motor drive receives a RUN command, it enables the
corresponding output terminal (setting 12) after Pr.02-29 time. It
checks if this function is enabled in the detection time
(Pr.02-35). If NOT, the mechanical brake error occurs and error
code “MBF” displays.
43
EPS function (Emergency
Power System)
If power is cut during running, the drive stops when the DC bus
voltage is less than the low voltage level. After power is cut, the
drive runs according to the EPS frequency when EPS is applied
and this function is ON.
44
Mechanical brake 2
When the motor drive receives a RUN command, it enables the
corresponding output terminal (setting 12) after Pr.02-29 time. It
checks if this function is enabled in the detection time
(Pr.02-35). If NOT, the mechanical brake error occurs and error
code “MBF” displays.
45–51
Direct docking mode only
Contact Delta for more information.
53
Terminal leveling signal for
direct docking
When the elevator runs to the leveling area, controller sends a
signal to the drive to make the drive stop within effective
distance (Pr.01-36).
54
Power failure signal
When power failure occurs, the host controller inputs this signal
to inform the drive. When the motor drive receives this signal,
MO = 49 is disabled after Pr.06-71 time
55
Manual emergency
deceleration
When the motor drive receives this signal, it decelerates to
Pr.01-29 speed according to Pr.01-40 deceleration time.
56
Automatic emergency
deceleration
After setting this MI function, the system monitors the current
speed. If the speed is higher than Pr.01-39, the drive
decelerates to Pr.01-29 speed according to Pr.01-40
deceleration time.
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...