Ch12 Descriptions of Parameter Settings
| VFD-ED
12-45
Over-current Stall Prevention during Operation
Control Mode
VF
VFPG
SVC
Default:
0
Settings
0: Disable
0–250% (rated current of the motor drive)
If the output current exceeds the setting specified in Pr.06-03 when the drive is operating, the drive
decreases its output frequency according to the Pr.06-04 setting to prevent motor stall. If the output current
is lower than the setting in Pr.06-03, the drive accelerates (according to Pr.06-04) again to catch up with
the Frequency command value.
Over-Current
Detection Level
06-03
Output Current
Output
Frequency
Over-Current Stall
Prevention during
Operation, output
frequency decrease
over-current stall prevention during operation
Time
Acceleration/Deceleration Time for Stall Prevention at Constant Speed
Control Mode
VF
VFPG
SVC
Default:
0
Settings
0: Use the current acceleration/deceleration time
1: Use the 1st acceleration/deceleration time
2: Use the 2nd acceleration/deceleration time
3: Use the 3rd acceleration/deceleration time
4: Use the 4th acceleration/deceleration time
5: Use the auto-acceleration/auto-deceleration time
Sets the acceleration/deceleration time when stall prevention occurs at constant speed.
Over-torque Detection (OT1)
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
0: Over-torque detection disabled
1: Over-torque detection during constant speed operation, continue to operate after
detection
2: Over-torque detection during constant speed operation, stop operating after
detection
3: Over-torque detection during operation, continue to operate after detection
4: Over-torque detection during operation, stop operating after detection
Over-torque Detection Level (OT1)
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
150
Settings
10–250% (rated current of the motor drive)
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...