Ch12 Descriptions of Parameter Settings
| VFD-ED
12-4
User-defined Coefficient K
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
Digit 4: number of decimal points (0–3)
Digit 0–3: 40–9999
Digital setting method
Digital 4: number of decimal points (0: no decimal points, 1: one decimal point and so on.)
Digit 0–3: 40–9999 (the corresponding value for the maximum frequency).
Meaning of numerical order
00000
Decimal Point Number
Corresponding Value
For example, if you use rpm to display the motor speed, and the corresponding value for the four-pole
motor, 60 Hz is 1800. You can set this parameter to 1800 to indicate that the corresponding value for 60
Hz is 1800 rpm. If the unit is rps, set to 10300 to indicate that the corresponding value for 60 Hz is 30.0
(one decimal point).
The frequency setting only displays as the rpm value. For example, 60 Hz is displayed as 1800 rpm.
After you set Pr.00-05, the keypad does not display the frequency unit “Hz” after returning to the Main
menu.
Software Version
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
##.##
Settings
Read Only
Password Input
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
1–9998, 10000–65535
Display
0–2 (number of wrong password attempts)
Inputs the password that is set in Pr.00-08. Enter the correct password here to enable changing
parameters. You are limited to a maximum of three attempts. After three consecutive failed attempts,
“Password Error” is displayed, and you must restart the AC motor drive before you can try again to enter
the correct password.
If you forget the password, you can decode by setting this parameter to 9999 and press the PROG/DATA
button (
PROG
DATA
) twice. Note that this resets the settings to the default.
Password Set
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
1–9998, 10000–65535
Display
0: No password set or successful input in Pr. 00-07
1: Password has been set
This parameter is for setting the password protection. Password can be set directly the first time. After you
set the password, the value of Pr.00-08 is 01, which means password protection is activated. However, if
the value of Pr.00-08 is 00, the password protection is deactivated, which means you can change any of
the parameter settings (including resetting the parameter protection password for Pr.00-08). When
Pr.00-08 is 01 and if you want to change any of the parameter settings, you must enter the correct
password in Pr.00-07 to deactivate the password, and this would make Pr.00-08 become 00. Note that if
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...