Ch12 Descriptions of Parameter Settings
| VFD-ED
12-66
Frequency
Time
Dwell at accel./decel.
07-08
Dwell
Frequency
at Accel.
07-07
Dwell Time
at Accel.
07-09
Dwell Time
at Decel.
07-10
Dwell
Frequency
at Decel.
Cooling Fan Control
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
2
Settings
0: Cooling fan is always ON
.
1: One minute after AC motor drive stops, cooling fan is OFF
.
2: AC motor drive runs and cooling fan is ON; AC motor drive stops and cooling fan
is OFF
.
3: Cooling fan is ON to run when preliminary IGBT temperature (
℃
) reached
.
4: Cooling fan is always OFF
.
Use this parameter for the fan control.
When set to 3, the fan starts to run until the heat sink temperature is less than 40°C if temperature exceeds
40°C.
Torque Command
Control Mode
Default:
0.0
Settings
-150.0–150.0% (Pr.07-14 setting = 100%)
This parameter sets the Torque command. When Pr.07-14 is 250% and Pr.07-12 is 100%, the actual Torque
command = 250x100% =250% of the motor rated torque.
Torque Command Source
Control Mode
Default:
2
Settings
0: Use the KPC-CC01 digital keypad
1: Use the RS-485 serial communication
2: Use the analog signal (Pr.03-00)
Specifies the Torque command source (Torque command is in Pr.07-12).
Maximum Torque Command
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
100
Settings
0–300% of the rated motor drive torque
Sets the maximum Torque command value (the motor rated torque is 100%).
Torque Command Filter Time
Control Mode
Default:
0.000
Settings
0.000–1.000 sec.
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...