Ch12 Descriptions of Parameter Settings
| VFD-ED
12-7
Automatic Voltage Regulation (AVR) Function
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
0: Enable AVR
1: Disable AVR
2: Disable AVR when decelerating to stop
The AVR function automatically regulates the AC motor drive output voltage to the motor’s rated voltage
when the input power is larger than the motor’s rated voltages. For instance, if you set V/F curve to 200
V
AC
/50 Hz and the input voltage is between 200
–
264 V
AC
, then the output voltage to the motor is
automatically regulated to 200 V
AC
/50 Hz. If the input voltage is from 180 to 200 V
AC
, the output voltage to
the motor and the input voltage is in direct proportion to the input voltage.
When the motor stops with deceleration, it shortens the deceleration time with AVR disabled. Setting this
parameter to 1 with auto-acceleration/auto-deceleration results in quicker deceleration.
Master Frequency Command Source
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:1
Settings
1: RS-485 serial communication or digital keypad (KPC-CC01)
2: External analog input (Pr.03-00)
3: Digital terminal inputs
4: Direct docking mode only, contact Delta for more information.
Determines the drive’s master frequency source.
Operation Command Source
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:1
Settings
1: External terminals
2: RS-485 serial communication or digital keypad (KPC-CC01)
The ED series motor drives are shipped without a digital keypad, but you can use the external terminals or
RS-485 to control the operation command.
When the LED PU is ON, you can control the operation command with the optional digital keypad. (Refer to
Chapter 09 for more information about the digital keypad KPC-CC01).
Содержание VFD-ED Series
Страница 3: ......
Страница 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Страница 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Страница 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Страница 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Страница 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Страница 32: ...Ch03 Wiring VFD ED 3 5...
Страница 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Страница 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Страница 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Страница 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Страница 93: ...06 Optional Accessories VFD ED 6 42 EMC Filter Model B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Страница 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Страница 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Страница 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Страница 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Страница 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Страница 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Страница 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Страница 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Страница 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Страница 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...