Chapter 5 Trial Run and Tuning Procedure
|
ASDA-A&A+ Series
Revision April 2009
5-9
5.4 Speed Trial Run without Load
Before speed trial run, fix and secure the motor as possible to avoid the danger from the reacting
force when motor speed changes.
STEP 1:
Set the value of parameter P1-01 to 02 and it is speed (S) control mode. After selecting the operation mode
as speed (S) control mode, please restart the drive as P1-01 is effective only after the servo drive is restarted
(after switching power off and on).
STEP 2:
In speed control mode, the necessary Digital Inputs are listed as follows:
Digital Input
Parameter Setting
Value
Sign
Function Description
CN1 PIN No.
DI1 P2-10=101
SON
Servo
On
DI1-=9
DI2
P2-11=109
TRQLM
Torque limit enabled
DI2-=10
DI3
P2-12=114
SPD0
Speed command selection
DI3-=34
DI4
P2-13=115
SPD1
Speed command selection
DI4-=8
DI5 P2-14=102
ARST
Reset
DI5-=33
DI6
P2-15=0
Disabled
This DI function is disabled
-
DI7
P2-16=0
Disabled
This DI function is disabled
-
DI8
P2-17=0
Disabled
This DI function is disabled
-
By default, DI6 is the function of reverse inhibit limit, DI7 is the function of forward inhibit limit and DI6 is the
function of emergency stop (DI8), if the users do not set the setting value of parameters P2-15 to P2-17 to 0
(Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to
Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value
of parameters P2-15 to P2-17 to 0 (Disabled) in advance.
All the digital inputs of Delta ASDA-A series are user-defined, and the users can set the DI signals freely.
Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please
refer to Table 7.A in Chapter 7). If any alarm code displays after the setting is completed, the users can
restart the drive or set DI5 to be activated to clear the fault. Please refer to section 5.2.
The speed command is selected by SPD0, SPD1. Please refer to the following table:
DI signal of CN1
Speed
Command No.
SPD1
SPD0
Command Source
Content
Range
S1 0
0
External analog
command
Voltage between V-REF
and GND
+/- 10V
S2 0
1
P1-09 +/-
5000r/min
S3 1
0
P1-10 +/-
5000r/min
S4 1
1
Internal parameter
P1-11 +/-
5000r/min
0: indicates OFF (Normally Open); 1: indicates ON (Normally Closed)