Chapter 7 Servo Parameters
|
ASDA-A&A+ Series
7-24
Revision April 2009
P0 - 09
MAP0
Block Data Read / Write Register 0
Communication Addr.: 0009H
Default: 407H
Related Section: N/A
Applicable Control Mode: ALL
Unit: N/A
Range: 100H ~ 417H
Settings:
Set the register address in HEX that users want to read and write by using the keypad.
Users can enter the desired register address (0100H ~ 0417H) into P0-09 to P0-16 (0009H ~
0010H). Then, users can read and write up to 8 continuous specified block data from the
communication address 0009H to 0010H through the communication port.
For example, if setting P0-09 to 407 by using the keypad, when the users read and write the
data from communication address 0009H, it means that the read and write value is the setting
value of parameter P4-07.
P0 - 10
MAP1
Block Data Read / Write Register 1
Communication Addr.: 000AH
Default: 10FH
Related Section: N/A
Applicable Control Mode: ALL
Unit: N/A
Range: 100H ~ 417H
Settings: See P0-09 for explanation.
P0 - 11
MAP2
Block Data Read / Write Register 2
Communication Addr.: 000BH
Default: 110H
Related Section: N/A
Applicable Control Mode: ALL
Unit: N/A
Range: 100H ~ 417H
Settings: See P0-09 for explanation.
P0 - 12
MAP3
Block Data Read / Write Register 3
Communication Addr.: 000CH
Default: 224H
Related Section: N/A
Applicable Control Mode: ALL
Unit: N/A
Range: 100H ~ 417H
Settings: See P0-09 for explanation.