Chapter 7 Servo Parameters
|
ASDA-A&A+ Series
Revision April 2009
7-27
Group 1: P1-xx Basic Parameters
P1 - 00
▲
PTT
External Pulse Input Type
Communication Addr.: 0100H
Default: 2
Related Section:
Applicable Control Mode: Pt
Section 6.2.1
Unit: N/A
Range: 00 ~ 132 (ASDA-A series)
00 ~ 1132 (ASDA-A+ series)
Settings:
ASDA-A series:
not used
A
B
C
ASDA-A+ series:
D
A
B
C
not used
•
A: Pulse type
A=0: AB phase pulse (4x)
A=1: CW + CCW pulse
A=2: Pulse + Direction
Other
setting:
Reversed
•
B: Input pulse filter
B=0:
500Kpps
B=1:
200Kpps
B=2:
150Kpps
B=3:
80Kpps
This setting is used to suppress or reduce the
chatter caused by the noise, etc. However, if the
instant input pulse filter frequency is over high,
the frequency that exceeds the setting value will
be regarded as noise and filtered.
•
C: Logic type
0=Positive Logic
1=Negative Logic
Pulse Type
Forward
Reverse
Forward
Reverse
AB phase pulse
CW + CCW pulse
Pulse + Direction
Input pulse interface
Max. input pulse frequency
Line driver
500Kpps
Open collector
200Kpps