Chapter 7 Servo Parameters
|
ASDA-A&A+ Series
7-34
Revision April 2009
P1 - 17
PO2H 2nd Position Command for Rotation
Communication Addr.: 0111H
Default: 0
Related Section:
Applicable Control Mode: Pr
Section 6.2.2
Unit: rev
Range: -30000 ~ +30000
Settings:
This parameter is used to set rotation cycle number of internal position 2.
P1 - 18
PO2L
2nd Position Command for Pulse
Communication Addr.: 0112H
Default: 0
Related Section:
Applicable Control Mode: Pr
Section 6.2.2
Unit: pulse
Range: +/-max. cnt/rev
Settings:
This parameter is used to set rotation pulse number of internal position 2.
Stroke2 = PO2H × (cnt/rev) + PO2L
P1 - 19
PO3H 3rd Position Command for Rotation
Communication Addr.: 0113H
Default: 0
Related Section:
Applicable Control Mode: Pr
Section 6.2.2
Unit: rev
Range: -30000 ~ +30000
Settings:
This parameter is used to set rotation cycle number of internal position 3.
P1 - 20
PO3L
3rd Position Command for Pulse
Communication Addr.: 0114H
Default: 0
Related Section:
Applicable Control Mode: Pr
Section 6.2.2
Unit: pulse
Range: +/-max. cnt/rev
Settings:
This parameter is used to set rotation pulse number of internal position 3.
Stroke3 = PO3H × (cnt/rev) + PO3L