Chapter 7 Servo Parameters
|
ASDA-A&A+ Series
7-12
Revision April 2009
Position Control
Control
Mode
Parameter Name
Function
Default Unit
Pt Pr S T
Related
Section of
User
Manual
P1-01
●
CTL
Control Mode and Output Direction
0
pulse
r/min
N-m
{
{
{
{
6.1
P1-02
▲
PSTL Speed and Torque Limit
0
N/A
{
{
{
{
6.6
P1-46
▲
GR3
Encoder Output Pulse Number
1
pulse
{
{
{
{
---
P1-55
MSPD Maximum Speed Limit
rated
speed
r/min
{
{
{
{
---
1st ~ 3rd Torque Command
P1-12
~ P1-14
TQ1 ~
3
1st ~ 3rd Torque Limit
100 %
{
{
{
{
6.4.1
P2-50
DCLR Pulse Deviation Clear Mode
0
N/A
{
{
---
External pulse control command (Pt mode)
P1-00
▲
PTT
External Pulse Input Type
2
N/A
{
6.2.1
P1-44
▲
GR1
Electronic Gear Ratio (1st
Numerator) (N1)
1 pulse
{
{
6.2.5
P1-45
▲
GR2
Electronic Gear Ratio
(Denominator)
1
pulse
{
{
6.3.6
P2-60 GR4
Electronic Gear Ratio (2nd
Numerator) (N2)
1 pulse
{
{
Table
7.A
P2-61 GR5
Electronic Gear Ratio (3rd
Numerator) (N3)
1 pulse
{
{
Table
7.A
P2-62 GR6
Electronic Gear Ratio (4th
Numerator) (N4)
1 pulse
{
{
Table
7.A
Internal pulse control command (Pr mode)
PO1H
~
PO8H
1st ~ 8th Position command for
Rotation
P1-15
~ P1-30
PO1L ~
PO8L
1st ~ 8th Position command for
Pulse
0 N/A
{
6.2.2
P2-36
~ P2-43
POV1
~ POV8
Moving Speed Setting of 1st ~ 8th
Position
1000 r/min
{
6.2.2
P1-33
●
POSS
Position Control Mode (Pr)
0 N/A
{
6.2.2
P1-47 HMOV
Homing
Mode
00 N/A
{
{
{
{
12.8
P1-48 HSPD1
1st Speed Setting of High Speed
Homing
1000 r/min
{
{
{
{
12.8
P1-49 HSPD2
2nd Speed Setting of Low Speed
Homing
50 r/min
{
{
{
{
12.8
P1-50
HOF1 Homing Offset Rotation Number
0
rev
{
{
{
{
---
P1-51
HOF2 Homing Offset Pulse Number
0
pulse
{
{
{
{
---
P1-62 COKT
Delay Time of Internal Position
Command Completed Output
Signal
0 ms
{
---