Chapter 5 Trial Run and Tuning Procedure
|
ASDA-A&A+ Series
Revision April 2009
5-11
5.5 Position Trial Run without Load
Before position trial run, fix and secure the motor as possible to avoid the danger from the reacting
force when the motor speed changes.
STEP 1:
Set the value of parameter P1-01 to 01 and it is position (Pr) control mode. After selecting the operation
mode as position (Pr) control mode, please restart the drive and the setting would be valid.
STEP 2:
In position control mode, the necessary DI setting is listed as follows:
Digital Input
Parameter Setting
Value
Sign
Function Description
CN1 PIN No.
DI1 P2-10=101
SON
Servo
On
DI1-=9
DI2 P2-11=108
CTRG Command
trigged DI2-=10
DI3
P2-12=111
POS0
Position command selection
DI3-=34
DI4
P2-13=112
POS1
Position command selection
DI4-=8
DI5 P2-14=102
ARST
Reset
DI5-=33
DI6
P2-15=0
Disabled
This DI function is disabled
-
DI7
P2-16=0
Disabled
This DI function is disabled
-
DI8
P2-17=0
Disabled
This DI function is disabled
-
By default, DI6 is the function of reverse inhibit limit, DI7 is the function of forward inhibit limit and DI6 is the
function of emergency stop (DI8), if the users do not set the setting value of parameters P2-15 to P2-17 to 0
(Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to
Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value
of parameters P2-15 to P2-17 to 0 (Disabled) in advance.
All the digital inputs of Delta ASDA-A series are user-defined, and the users can set the DI signals freely.
Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please
refer to Table 7.A in Chapter 7). If any alarm code displays after the setting is completed, the users can
restart the drive or set DI5 to be activated to clear the fault. Please refer to section 5.2.
For the information of wiring diagram, please refer to Section 3.6.2 (Wiring of position (Pr) control mode).
Because POS2 is not the default DI, the users need to change the value of parameter P2-14 to 113.