13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[24]
Comparator 2
Use the result of comparator 2 in the
logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the
logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the
logic rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the
logic rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[30]
SL Time-out 0
Use the result of timer 0 in the logic
rule.
[31]
SL Time-out 1
Use the result of timer 1 in the logic
rule.
[32]
SL Time-out 2
Use the result of timer 2 in the logic
rule.
[33]
Digital input DI18
Use the value of DI18 in the logic
rule (High = TRUE).
[34]
Digital input DI19
Use the value of DI19 in the logic
rule (High = TRUE).
[35]
Digital input DI27
Use the value of DI27 in the logic
rule (High = TRUE).
[36]
Digital input DI29
Use the value of DI29 in the logic
rule (High = TRUE).
[37]
Digital input DI32
Use the value of DI32 in the logic
rule (High = TRUE).
[38]
Digital input DI33
Use the value of DI33 in the logic
rule (High = TRUE).
[39]
Start command
This logic rule is TRUE if the
frequency converter is started by any
means (either via digital input, field
bus or other).
[40]
Drive stopped
This logic rule is TRUE if the
frequency converter is stopped or
coasted by any means (either via
digital input, fieldbus or other).
[41]
Reset Trip
This logic rule is TRUE if the
frequency converter is tripped (but
not trip-locked) and the reset button
is pressed.
[42]
Auto Reset Trip
This logic rule is TRUE if the
frequency converter is tripped (but
not trip-locked) and an Automatic
Reset is issued.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[43]
OK Key
This logic rule is TRUE if the OK key
on the LCP is pressed.
[44]
Reset Key
This logic rule is TRUE if the Reset
key on the LCP is pressed.
[45]
Left Key
This logic rule is TRUE if the Left key
on the LCP is pressed.
[46]
Right Key
This logic rule is TRUE if the Right
key on the LCP is pressed.
[47]
Up Key
This logic rule is TRUE if the Up key
on the LCP is pressed.
[48]
Down Key
This logic rule is TRUE if the Down
key on the LCP is pressed.
[50]
Comparator 4
Use the result of comparator 4 in the
logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the
logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the
logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic
rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic
rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic
rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic
rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic
rule.
[76]
Digital Input x30 2
[77]
Digital Input x30 3
[78]
Digital Input x30 4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[100] Fire Mode
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark