18-12 Fire Mode Log: Date and Time
Range:
Function:
Size
related
*
[ 0 -
0 ]
This parameter contains an array with 10
elements. The parameter shows at which
date and time the logged event occurred.
The function relies on that the actual date
and time has been set in
. Note: There is no build in battery
back up of the clock. An external back up
must be used, eg the one in the MCB 109
Analog I/O option card. See Clock Settings,
0-7*.
3.17.3 18-3* Analog I/O
Parameters for reporting the digital and analog I/O ports.
18-30 Analog Input X42/1
Range:
Function:
0.000
*
[-20.000 -
20.000 ]
Read out of the value of the signal
applied to terminal X42/1 on the Analog
I/O Card.
The units of the value shown in the LCP
will correspond to the mode selected in
18-31 Analog Input X42/3
Range:
Function:
0.000
*
[-20.000 -
20.000 ]
Read out of the value of the signal
applied to terminal X42/3 on the Analog
I/O Card.
The units of the value shown in the LCP
will correspond to the mode selected in
18-32 Analog Input X42/5
Range:
Function:
0.000
*
[-20.000 -
20.000 ]
Read out of the value of the signal
applied to terminal X42/5 on the Analog
I/O Card.
The units of the value shown in the LCP
will correspond to the mode selected in
18-33 Analog Out X42/7 [V]
Range:
Function:
0.000
*
[0.000 -
30.000 ]
Read out of the value of the signal
applied to terminal X42/7 on the Analog
I/O Card.
The value shown reflects the selection in
18-34 Analog Out X42/9 [V]
Range:
Function:
0.000
*
[0.000 -
30.000 ]
Read out of the value of the signal
applied to terminal X42/9 on the Analog
I/O Card.
The value shown reflects the selection in
.
18-35 Analog Out X42/11 [V]
Range:
Function:
0.000
*
[0.000 -
30.000 ]
Read out of the value of the signal
applied to terminal X42/11 on the
Analog I/O Card.
The value shown reflects the selection in
.
3.17.4 18-5* Ref. & Feedb.
NOTE
Sensorless Readout requires set up by MCT 10 with
sensorless specific plug in.
18-50 Sensorless Readout [unit]
Range:
Function:
0.000 SensorlessUnit
*
[-999999.999 - 999999.999
SensorlessUnit]