8-31 Address
Range:
Function:
Size related
*
[ 1. - 255. ] Enter the address for the FC
(standard) port.
Valid range: 1 - 126.
8-32 Baud Rate
Option:
Function:
Baud rates 9600, 19200, 38400 and 76800
baud are valid for BacNet only.
[0]
2400 Baud
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol
using the FC Port. For
some of the protocols, not all
options will be visible. Default
depends on the protocol selected.
[0]
*
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-34 Estimated cycle time
Range:
Function:
0 ms
*
[0 -
1000000 ms]
In a noisy environments, the interface may
be blocked by due to overload of bad
frames. This parameter specifies the time
between two consecutive frames on the
network. If the interface does not detect
valid frames in that time it flushes the
receive buffer.
8-35 Minimum Response Delay
Range:
Function:
Size related
*
[ 5. - 10000.
ms]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is
used for overcoming modem
turnaround delays.
8-36 Maximum Response Delay
Range:
Function:
Size related
*
[ 11. - 10001.
ms]
Specify the maximum permissible
delay time between transmitting a
request and receiving a response.
Exceeding this delay time will cause
control word time-out.
8-37 Maximum Inter-Char Delay
Range:
Function:
Size related
*
[ 0.00 - 35.00
ms]
Specify the maximum permissible
time interval between receipt of
two bytes. This parameter activates
time-out if transmission is
interrupted.
3.9.4 8-4* Telegram Selection
8-40 Telegram Selection
Option:
Function:
Enables use of freely configurable
telegrams or standard telegrams for
the FC port.
[1]
*
Standard telegram 1
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
[107] PPO 7
[108] PPO 8
[200] Custom telegram 1
8-42 PCD write configuration
Range:
Function:
Application dependent
*
[0 - 9999 ]
8-43 PCD read configuration
Range:
Function:
Application dependent
*
[0 - 9999 ]
Parameter Description
VLT
®
HVAC Drive Programming Guide
84
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
3