23-65 Minimum Bin Value
Range:
Function:
Size
related
*
[ 0 -
100. %]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
▲
and
▼
buttons on the LCP.
Set the minimum limit for each interval in
and
. Example: if selecting
counter
[1]
and changing setting from 10% to 12%,
counter
[0] will be based on the interval 0 -
<12% and
counter
[1] on interval 12% -
<20%.
23-66 Reset Continuous Bin Data
Option:
Function:
[0]
*
Do not reset Select
Do reset
[1] to reset all values in
.
After pressing OK the setting of the
parameter value will automatically change to
Do not reset
[0].
[1]
Do reset
23-67 Reset Timed Bin Data
Option:
Function:
Select
Do reset
[1] to reset all counters in
.
After pressing OK the setting of the parameter
value will automatically change to
Do not reset
[0].
[0] Do not reset
[1] Do reset
Parameter Description
VLT
®
HVAC Drive Programming Guide
168
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
3
3